AlertMaxx2 Error Code Card
-
How do I connect an external device to the AlertMaxx2 volt free relay?
To connect an external device simply link out the IN and +6V (shown below), then use the NO and GND to wire in the device in question. Black (-) to GND and red (+) to NO. If the device is to be pow...
-
What type RCBO should I use?
We recommend a Type C RCBO. This device is the normal choice for commercial and industrial applications where some degree of electrical inrush is expected (i.e. an induction motor).
-
How do I install a Dual V3, AlertMaxx2 and PowerMaxx2?
-
Does the AlertMaxx2 and PowerMaxx2 have to be put in a fire proof cupboard?
No, the AlertMaxx2 enclosure is fire retardant (UL94 VO) and the PowerMaxx2 is enclosed in a metal casing.
-
Does the AlertMaxx2 require a separate supply to power it?
No, the AlertMaxx2 is powered by the mains cables that you would have provided power to the pumps with. The AlertMaxx2 is fitted as a junction box as per the wiring schematic here.
-
When installing my AlertMaxx2, I get a constant F1 code, why?
There are a few possible reasons for a constant F1 code. The float switch isn't wired in. The finger float switch is upside down in the housing. If using a pendant float switch, the wrong cores ha...
-
AlertMaxx2 Wi-Fi Reconnection Guide (SEU1)
-
AlertMaxx2 Wi-Fi Reconnection Guide (SEU2)
-
My AlertMaxx2/Rego1 has an EC code?
An EC code on an AlertMaxx2/Rego1 means an error in Wi-Fi configuration, normally caused by a change in network name or password. If your AlertMaxx2 or Rego1 has an aerial protruding from the left ...